Addressable system
design secrets:
·
Distance between Smoke
Detector mustn’t exceed 10 m to avoid dead area between detectors
·
Distance between heat
Detector mustn’t exceed 7 m to avoid dead area between detectors
·
Fire detector must be mounted
at least one meter from any forced air inlet.
·
Ramps at car parking must
be covered by heat detectors
·
Voice evacuation located at
escape stair must be in a separate loop.
·
Fire fighter telephone must
be located at elevator lobbies & pump rooms.
·
Each fire loop must have
20% spare capacity.
·
Access control system ( ACS
), elevator, Door holder,Public address system ( PA ), exhaust fan’s, Air
Handling Units( AHU’S ) connected to fire alarm system via control module ( CM
)
·
Fire fighting system(
FM200, CO2, Sprinkler system( flow switch & Tamper switch ) ) connected to
fire alarm system via monitor module ( MM ).
·
Alarm bell located at
2200mm above finished floor level.